Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Conductivity:
Measuring range: 0.01~20.00, 200.0, 2000µS/cm, 20.00, 200.0mS/cm
Display resolution: 0.001, 0.01, 0.1, 1
Measurement accuracy: ±1% FS
Calibration point: 1 to 3 points
Calibration solution: 84uS, 1413uS, 12.88mS, 111.8mS
TDS:
Measuring range: 0~10.00, 100.0, 1000ppm, 10.00, 200.0ppt
Display resolution: 0.01, 0.1, 1
Measurement accuracy: ±1% FS
TDS conversion factor: 0.1 to 1.0 (default 0.5)
Temperature:
Measuring range: 0~100°C/32~212°F
Display resolution: 0.1°C/0.1°F
Measurement accuracy: ±1°C/±1.8°F
Offset calibration: 1 point, measured value ±10°C
Communication:
Signal output: 4~20mA
Load Max: 500Ω
High/low alarm: 0.02uS/cm~20.0mS/cm, optional
Communication output: RS485
General parameters:
Temperature compensation range: 0~100°C/32~212°F, automatic
Temperature compensation coefficient: Linearity (0.0~10.0%/°C)
Reference temperature: 25°C
Conductivity cell constant: K=0.1, 1, 10
Environmental conditions: Ambient temperature<60°C, relative humidity<80%
Power type: DC24V
Dimensions: 96(L)×96(W)×75(H)mm
Meter weight: 350g