Rated voltage range of SLC input power (S+,S-): 22.0 to 24.0V
Maximum SLC 24 VDC standby current (S+,S-): 250µA
Maximum SLC 24 VDC alarm current (S+,S-): 250µA
IDC input circuit wiring style: Class B (Style B)
End-of-line resistor for IDC: 5.1kΩ, 1/2W
Maximum wiring resistance of IDC: 100Ω
Maximum wiring capacitance of IDC: 1µF
Operating temperature range: 0°C to 49°C (32°F to 120°F)
Operating humidity range: 0 to 93% (non-condensing)
Dimensions: 65.5mm (2.58 inches) (H) × 59mm (2.32 inches) (W) × 24mm (0.94 inch) (D)
Applicable electrical box for installation: North American 64mm (2-1/2 inches) deep single-gang box