Measuring Gas: Hydrogen (H2)
Measuring Principle: Chronoamperometry
Sampling Method: Suction type Approx. 0.6L/min (at room temperature with 2.4m gas sampling tube with a sampling probe)
Measuring Range: 0-100%LEL
Resolution: 1%LEL
Detectable accuracy: ±10%LEL
Concentration display: LCD Digital
Aralm accuracy: ±10%LEL
Alarm Concentration: 20%LEL
Alarm Method: LCD display, LED Lamp and Buzzer
Response Time: Within 25 seconds at 90% response from sampling gas inlet at 20°C
Operating Temperature Range: -10-40°C; below 95%RH (non-condensing)
Explosionproof: ExiaII CT4X(No.TC19531)
Pressure range: 80-110kPa
Power Source: 3 × "AA" size Alkaline batteries(LR6)
Continuous Operation time: Alkaline batteries : approx. 20 hrs (no alarm)
Main Body Dimensions: 78 (W) X 200 (H) X 50 (D)mm
Main Body Weight: Approx. 550g (including batteries)
Standard Accessories: Gas sampling tube with sampling probe(2.4m), leather case, carrying case