For full functionality of this site it is necessary to enable JavaScript.
EMIN.CO.TH
0
Product image

HV HIPOT GDTF-225/50 AC Resonant Test System For Generators (0-50kV; 225kVA)

ModelGDTF-225/50
OriginChina
Warranty12 months
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Rated output voltage: 0 ~ 50kV (RMS) or below.

Output frequency: 45 - 300Hz.

Waveform: pure sine wave, THD ≤ 1%.

Max. capacity: 2000kVA or below.

Duty cycle: continuous working 15mins one time at full power output.

Quality factor: 10 - 40.

Frequency adjustment sensitivity: 0.1HZ, instability of <0.05%.

Power supply: 220V or 380V ± 15%, 50HZ ± 5%.

Input voltage (V): 380

Output voltage (kV): 0-50

Capacity (kVA): 225

Application scope:

Generator--capacitance to the ground 0.2-0.27 μF

10 kV (300 mm² ) cable ≤ 2.5 km

Main configurations:

Fixed reactor 1 set

50kV/1A Adjustable reactor 1 set

Capacitive divider 50kV