Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Measurement ranges:
+ CO2: 0–2000 ppm / 400–2000 ppm (selectable via jumper)
+ VOC:
CO₂eq: 400–2000 ppm
TVOC ppm: 0–30.0 ppm
TVOC µg/m3: 0–10000 µg/m3
IAQ index: 1–5 (UBA rating)
+ Temperature: 0...50 °C
+ Relative humidity: 0–100 %rH
Accuracy:
+ CO2: ±43 ppm + 3 % of reading (typical), additional ±60 ppm for first weeks
+ VOC*: 15 % of reading (typical)
*VOC sensor is tuned for typical IAQ Mix of 22 VOCs as defined by Mølhave et al. (1997)
+ Temperature: ±0.5 ⁰C (typical at 20 ⁰C)
+ Relative humidity: ±2.4 %rH (typical at 20 ºC, 30 % rH)
Measuring elements:
+ CO2: Non-dispersive infrared (NDIR)
+ VOC: Complementary Metal Oxide Semiconductor (CMOS)
+ PM: Laser-based light scattering particle sensing
+ Temperature: Integrated to CMOS
+ Relative humidity: Thermoset polymer capacitive sensing element
Measuring units:
+ CO2: ppm
+ Relative humidity: % rH
+ Temperature: °C
+ VOC: CO2eq: ppm; TVOC: ppm, μg/m3
+ PM1/2.5/10: μg/m3
Calibration (CO2): Automatic self-calibration, ABC LogicTM
Supply voltage: 24 VDC/VAC ±10 %
Output signal 1–4:0...10 V (optional 2...10 V / 0...5 V, display or configuration tool required); Optional: 4...20 mA; Linear to selected measurement (CO2, VOC, PM, rH or Temp)
Operating temperature: 0...50 °C
Protection standard: IP20
Noted:
CO2 = Carbon dioxide sensor
VOC = Volatile Organic Compounds sensor
rH = Humidity sensor
T = Temperature sensor,