Target: For overhead lines
Working voltage range: 22 kV - 42 kV
Operation starting voltage: 1500 V ±20%
Dielectric strength: Between insulating sticks 30 cm apart (75 kVAC, 1 minute) 2 places.
Leakage current: During dielectric strength test: 100 µA or less
Storage case: Portable case for storage
Frequency: 50/60 Hz
Insulation resistance: 2000 MΩ or more (Use of a 1000 V megger)
Phase test function: Detection of in-phase or different phase of 120 °
Phase sequence function: Detection of advance or delay of 120 °
Indicators
Light: Readable under brightness of 8000 lux
Sound: 50 dB or more at distance of 1 m from sound source (intermittent sound) (only on receiver side)
Operating temperature range: -10ºC - +40ºC
Distance for phase test:
6 m (3 m × 2) distance between transmitter and receiver with standard optical cables
Up to 30 m with the optical cable option
Battery: Two 1.5 V dry batteries (R1) each
Accessories
Storage case: Portable case for storage
Insulating stick: Telescopic type: Approx. 1,665 mm, 2 pcs
Contact tip hardware: Two metal hooks for suspension (attached at shipment); Two flat blades
Optical cable: 3 m coiled cord x 2 pcs
Optical cable joint: 1 piece