For full functionality of this site it is necessary to enable JavaScript.
EMIN.CO.TH
0
Product image

HANNA HI510-0540 Universal Process Controllers

USD 1,406.17
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Channels: 1

Display: Graphic LCD, 128 x 64 pixel B/W with backlight

Digital Inputs : 2 independent, galvanically isolated inputs (configurable for Hold & Cleaning functions)

On state: 5 to 24 Vdc, low or high level active

Analog Outputs:

2 or 4 independent, galvanically isolated outputs

0 – 22 mA configurable as:

0 – 20 mA

4 – 20 mA

22 mA as alarm signal

Analog Output Accuracy: ±0.2% f.s.

Digital Communication:

RS-485 serial port for remote monitoring and control (Modbus)

USB-C port to retrieve log files and firmware upgrading

Relays:

Up to 5 relays (independently configurable for process variables, Hold & Cleaning functions)

Electromechanical relay SPDT and SPST contact outputs

5A – 250 Vac; 5A – 30 Vdc (resistive load)

Fuse protected: 5A, 250V slow blow fuse

Alarm Relay for All Measurement Alarms

Electromechanical relay SPDT contact output

5A – 250 Vac; 5A – 30 Vdc (resistive load)

Fuse protected: 5A, 250V slow blow fuse

Data Logging:

Interval log, up to 100 files, maximum 8600 records on each stored file.When the maximum limit is reached, the most recent file will automatically erase the oldest one.

Event log, maximum 100 records. When the maximum limit is reached, the last record overwrites the oldest one.

Power Supply: 100 – 240 Vac ±10%; 50/60 Hz; 15VA; fuse protected (2A, 250V slow blow fuse)

Power Consumption : 15VA

Installation Category: II

Environment:  -20 to 50 ºC (-4 to 122 ºF); maximum 100% RH non-condensing

Enclosure*: Single case ½ DIN, IP65 ingress protection

Weight Approximately: 1.6 kg (3.5 lb.)

Dimensions Width: 144.0 mm (5.7”)

Height: 144.0 mm (5.7”)

Depth: 151.3 mm (6.0”)

HI510-0540 universal process controller with digital probe inputs, 5 relays, 4 analog outputs, RS-485 / Modbus serial communication protocol, 100-240 Vac is supplied with power cable, 3 m (9.84’) long; set of cable gland seals; instrument quality certificate; and quick reference guide with QR code for user manual download.