HANNA BL983315-0 TDS Mini Controller, range: 0.0 to 199.9 mg/L (ppm), dosing relay: contact closed when reading exceeds setpoint value, 12VDC
Range 0.0 to 199.9 ppm (mg/L)
Resolution 0.1 ppm (mg/L)
Accuracy (@25°C/77°F) ±2% full scale
TDS Conversion Factor 0.5
Calibration manual, with CAL trimmer
Dosing Relay maximum 2A (fuse protected), 250 VAC, 30 VDC
Dosing Selection relay activated (contact closed) when the measurement reading is greater than the setpoint
Setpoint adjustable from 0 to 199.9 ppm (mg/L)
Overtime adjustable, typically from 5 to approximately 30 minutes
Temperature Compensation automatic from 5 to 50°C (41 to 122°F) with beta =2%/ºC
Power Supply models “-0”: 12 VDC adapter (included)
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight models “-0”: 200 g (7.1 oz.)
Ordering Information and BL983315-0 (12 VDC) are supplied with mounting brackets, transparent cover and instruction manual