GENY YC1893D Meter Test System (3×(24V–480V), 1mA-120A)

ModelYC1893D
OriginChina
Warranty12 months
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Power supply

- Voltage: 3×230/400V±10%

- Frequency: 50/60Hz±2Hz

- Power capacity: >6kVA

Voltage

- Test voltage output (Phase-Neutral): 3×(24V–480V) or 600V F-F customized

- Power of the voltage output: 3×800VA

- Resolution: Better than 0.01% of the full-scale value of the range

- Setting accuracy: Better than 0.05% at the final range value

- Stability: Better than 0.005%/h (integration time 150s)

- Load regulation from 0-max. load: <0.01%

- Distortion factor: <0.3% for linear resistance load

- Harmonics: 2nd-41st free programmable

Current

- Test current output: 1mA-120A

- Power of the current output: 3×1200VA

Phase angle

- Range: 0°-360°

- Resolution: 0.01°

- Setting accuracy: 0.1°

Frequency

- Range: 45 Hz – 65 Hz

- Resolution: 0.01 Hz