Delivery Available

DCV: 1000 V /± 0.09%+2 dgt

ACV: 1000 V /±2%+3 dgt

DCA: 400mA /± 0.2%+2 dgt

ACA: 400mA /± 0.9%+2 dgt

R: 50 MΩ /±0.9%+2 dgt

C: 9,999 µF /±(1.2%+2)

F: 100 kHz /±(0.1%+1)

T type K:-40.0 °C to 537 °C (-40.0 °F to 998 °F)

Diode Test: yes

Test Voltages: 50, 100, 250, 500, 1000 V

Insulation resistance range: 2 GΩ

Size: 203 x 100 x 50 mm (with holster)

Weight: 624 g

IP Rating: IP40

Includes: Remote probe, K-type thermocouple, Test leads, Alligator clips, Hard case, Four AA alkaline batteries, Quick Reference Guide, CD Rom with Manual


Specifications
Voltage DC
Maximum Voltage:  1000 V
Accuracy:  1577: ±(0.2%+2)
   1587: ±(0.09%+2)
Maximum Resolution:  0.001V
Voltage AC
Maximum Voltage:  1000 V
Accuracy:  1577: ±(2%+3)
   1587: ±(2%+3)
AC Bandwidth:  1587: 5kHz*
   *with low pass filter; 3db @ 800 Hz
Maximum Resolution:  0.1 mV
Current DC
Maximum Amps:  400mA
Amps Accuracy:  1577: ±(1.0%+2)
   1587: ±(0.2%+2)
Maximum Resolution:  0.01 mA
Current AC
Maximum Amps:  400mA
Amps Accuracy:  1577: ±(2.0%+2)*
   1587: ±(1.5%+2)*
   * 1kHz bandwidth
Maximum Resolution:  0.01 mA
Resistance
Maximum Resistance:  50 MΩ
Accuracy:  1577: ±(1.2%+2)
   1587: ±(0.9%+2)
Maximum Resolution:  0.1Ω
Capacitance(1587 only)
Maximum Capacitance:  9,999 µF
Accuracy:  ±(1.2%+2)
Maximum Resolution:  1 nF
Frequency (1587 only)
Maximum Frequency:  100 kHz
Accuracy:  ±(0.1%+1)
Maximum Resolution:  0.01 Hz
Temperature Measurement (1587 only)
   -40.0 °C to 537 °C
   -40.0 °F to 998 °F
   excluding probe
Diode Test (1587 only)
Range:  6 V
Resolution:  1 mV
Accuracy:  ±(2 % + 1)
Insulation Test
Minimum Test Current @ 1kΩ/V:
   1mA
Test Voltages:
1577:  500, 1000 V
1587:  50, 100, 250, 500, 1000 V
Maximum Resistance per Test Voltage:
50V:  
100V:  
250V:  
500V:  
1000V:  1577: 600 MΩ
   1587: 2 GΩ
Maximum Resolution per Test Voltage:
50V:  0.01 MΩ
100V:  0.01 MΩ
250V:  0.1 MΩ
500V:  0.1 MΩ
1000V:  0.1 MΩ
Accuracy per Test Voltage:
50V:  ±(3 % + 5)
100V:  ±(3 % + 5)
250V:  ±(1.5 % + 5)
500V:  1577: ±(2.0 % + 5)
   1587: ±(1.5 % + 5)
1000V:  1577: ±(2.0 % + 5)
   1587: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ
Environmental Specifications
Operating temperature
   –20 °C to +55 °C
Storage temperature
   -40°C to +60°C
Humidity (Without Condensation)
   0% - 95% (10 °C – 30 °C)
   0% - 75% (30 °C – 40 °C)
   0% - 40% (40 °C – 55 °C)
Operating Altitude
   2000 m
Safety Specifications
Overvoltage category
   Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
Agency Approvals
   2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
Mechanical & General Specifications
Size
   203 x 100 x 50 mm (with holster)
Weight
   624 g
Warranty
   
Battery life Alkaline
Meter use:  1000 hours
Insulation test use:  Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating
   IP40

 

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts