- Number of channels: 4U / 4I
- Number of inputs: 5V / 4I
- IEC 61000-4-30: EN50160 reports
- Voltage (TRMS AC+DC): 2 V to 1,000 V
+ Voltage ratio: Up to 500 kV
- Current (TRMS AC+DC):
+ MN clamps: MN93 : 500 mA to 200 AAC ; MN93A : 0,005 AAC to 100 AAC
+ C193 clamp: 1 A to 1000 AAC
+ AmpFlex® or MA clamps: 100 mA to 10000 AAC
+ PAC93 clamp: 1 A to 1300 AAC/DC
+ E3N clamp: 50 MA to 100 AAC/DC
+ Current ratio: Up to 60 kA
- Frequency: 40 Hz to 69 Hz
- Power values: W, VA, var, VAD, PF, DPF, cos φ, tan φ
- Energy values : Wh, varh, VAh
- Harmonics : Yes
+ THD : Yes, orders 0 to 50, phase
+ Expert mode: Yes
- Transients : 210
- Flicker (Pst and Plt): Yes
- Inrush mode : Yes > 10 minutes
- Unbalance: Yes
- Recording Min/Max of a selection of parameters at max. sampling rate: 2 weeks to several years
- Alarm: 10,000 of 40 different types
- Peak: Yes
- Vectorial representation: Automatic
- Display: TFT colour ¼ VGA screen, 320 x 240, diagonal 148 mm
- Capture of screens and curves: 50
- Electrical safety: IEC 61010 1 000 V CAT III / 600 V CAT IV
- Protection : IP53 / IK08
- Battery life: Up to 13 hours
- Communication interface: USB
- Power supply: 9.6 V NiMH rechargeable battery or mains power supply
- EN50160 report: Yes with DataView®software
- Dimensions : 270 x 250 x 180 mm/3.7 kg
Models without sensors: delivered with bag no. 21, USB cable, IP67 mains power cable, 5 x 3 m black IP67 BB196 banana leads, 5 lockable crocodile clips, 12-colour identification kit for the leads and inputs, scratchproof screen-protection film (mounted), safety datasheet, CD containing the multi-language operating manual and CD PC data retrieval software and CD containing PC data retrieval software (Power Analyzer Transfer).